DMT-NVD217 High Voltage Contact Detector for Power Lines and Substations

  Remaining None only

Professional Dumatic High Voltage Detector designed for 11/36kV systems. Features rapid response, spark protection, and a rugged build, ensuring maximum safety for technicians in power plants and workshops.

 more information

SAR 2,300.00

+  

Earn loyalty points with this purchase

Rewards  

product sku

DOM0052

Weight

 kg

Quantity

This product is out of stock

Notify me when product is available

share product

product description

The Dumatic DMT-NVD217 is a critical safety tool for electrical technicians and substation contractors, providing a reliable method to detect high voltage through contact. It features a clear visual alert system via LEDs (Green for Armed, Red for Voltage Detected), integrated with advanced protection technology to prevent electrical bridging or sparking during inspection. This device comes in a heavy-duty protective carrying case, fully equipped for sustainable performance in the most demanding field environments.

 Key Features

  • Ultimate Safety: Equipped with built-in Bridging Protection and Spark Protection to ensure user safety during contact.

  • High Precision: Exceptional response time of less than 1 second for immediate decision-making.

  • Energy Efficient: Auto OFF feature after approximately 3 minutes to preserve battery life.

  • Smart Indicators: Dual LED system (Green = Armed / Ready, Red = Voltage Detected) for clear status communication.

  • Self-Test Function: Includes a dedicated Test/Arming Button to verify device functionality before use.

 Technical Specifications

  • Model: DMT-NVD217

  • System Voltage: 11/36kV

  • Threshold Set Within Range: 3.3kV to 4.95kV

  • Threshold Value: 4.12kV

  • Response Time: <1sec

  • Auto OFF: ±3min

  • Battery Current: <30mA

  • Battery Low Indicator: <7V

  • Dimensions: 300 (L) x 100 (W) x 100 (D) mm

  • Weight: Approx. 550g (battery included)


 Applications

  • Detecting live voltage in overhead transmission lines and substations.

  • Verifying circuits are de-energized before commencing maintenance work.

  • Essential safety tool for electrical emergency teams in construction projects.

  • Testing and maintaining medium to high voltage distribution panels.